TOXFREE® PLUS RZ1-K (AS+) 0.6/1kV is a power cable specially designed to transmit electrical energy…
Enhanced UV properties for TOXFREE® RZ1-K cable
The Toxfree® RZ1-K (AS) cable now has greatly improved ultraviolet (UV) radiation properties, according to the UNE 211605 climatic test. Due to its design the Toxfree® RZ1-K (AS) is a flexible and easy to handle cable, which guarantees maximum performance and safety in electrical installations in public areas.

DESIGN:
1 – Electrolytic annealed copper conductor, class 5 (flexible).
2 – Cross-linked polyethylene type XLPE.
3 – Low Smoke Halogen Free (LSZH) polyolefin outer sheath, type ST8.

WEATHER AND UV-RESISTANT OUTER SHEATH
The outer sheath, with improved ultraviolet radiation properties, gives this cable excellent weather resistance, allowing it to be installed outdoors without affecting its service life.


TECHNICAL CHARACTERISTICS OF TOXFREE® RZ1-K CABLE
TOXFREE® RZ1-K cable is known for its high performance: high flexibility, maximum electrical performance in indoor and outdoor installations, good resistance to maximum and minimum temperatures, impacts, chemical attacks and UV rays. All these characteristics guarantee a longer service life of the electrical installation:

Maximum fire performance CPR (B2ca, Cca)

Flexible cable

Halogen free

Minimum service temperature: -40ºC
A CABLE CLASSIFIED AS B2ca s1a, d1, a1
TOXFREE® RZ1-K (AS) is a 0.6/1kV Low Voltage cable designed from a flexible copper conductor (class 5), a flexible cross-linked polyethylene insulation and a flexible LSZH (halogen-free) polyolefin outer sheath, with low smoke emission and corrosive gases in case of fire.

The CPR classification of this cable is B2ca-s1a, d1, a1, according to European standard EN 50575. Certain cross-sections are classified as Cca-s1a, d1, a1.

TOXFREE® RZ1-K (AS)
Halogen free cable
FREQUENTLY ASKED QUESTIONS (FAQ) ABOUT THE TOXFREE® RZ1-K (AS) CABLE
What does CPR B2ca s1a,d1,a1 or Cca s1b,d1 a1 mean? How does the Construction Products Regulation (CPR) affect a cable?
Here you can find more information about the European Standard Construction Products Regulation (CPR) and its classification system for fire performance of electrical cables.
The CPR classification of TOP CABLE TOXFREE® PLUS RZ1-K (AS+) cable is B2ca-s1a,d1,a1 /Cca-s1b,d1,a1. In most European countries, the installation of minimum class Cca-s1b,d1,a1 cables is compulsory in public places such as: hospitals, schools, museums, airports, bus stations and shops in general.
What are the thermal performance of TOXFREE® ZH RZ1-K cable?
Maximum service temperature: 90ºC
Maximum short-circuit temperature: 250ºC (maximum 5 seconds)
Minimum service temperature: -40ºC (fixed and protected installations)
Minimum installation and handling temperature: 0°C (on cable surface)
Where can I find the cable technical specification in PDF format?
Here is the PDF of the summary technical specification of the TOXFREE® RZ1-K cable. If you need to consult additional technical aspects of this cable, such as its maximum admissible current or voltage drop, please contact us.